Pressure tank precharge: what should it be?

The precharge is the air pressure in the tank when it holds no water. Set it about 2 psi below the cut-in pressure: 28 psi for a 30/50 switch, 38 psi for 40/60 and 48 psi for 50/70. PressureTankCalc fills it in for you, or you can untick the box and type your own to see how a wrong precharge cuts the drawdown and makes the pump short cycle.

    Saved you some time? Leave a tip, entirely optional.

    Check it with a tire gauge at the air valve with the pump off and a tap open until the water stops.

    How the pressure tank calculator works

    PressureTankCalc treats the air in the tank as an ideal gas at constant temperature (Boyle’s law). With pressures converted to absolute by adding 14.7 psi, the share of the tank that is usable water between cut-out and cut-in is precharge × (1 ÷ cut-in − 1 ÷ cut-out). The precharge defaults to 2 psi below cut-in, the setting tank makers recommend. The drawdown you need is the pump flow × the minimum run time, 1 minute by default; dividing it by the drawdown factor gives the total tank volume, rounded up to a common size. Pump starts per hour peak when household use is half the pump flow: 60 × GPM ÷ (4 × drawdown).

    Drawdown by tank size and switch setting (gallons)

    Tank20/4030/5040/6050/70
    20 gal6.95.95.24.6
    32 gal119.48.37.3
    44 gal15.21311.310.1
    62 gal21.418.31614.2
    86 gal29.625.422.219.7
    119 gal4135.130.727.2

    Drawdown factor by switch setting

    SwitchPrechargeDrawdown factorTank per GPM (1 min run)
    20/40 psi18 psi0.3452.9 gal
    30/50 psi28 psi0.2953.4 gal
    40/60 psi38 psi0.2583.9 gal
    50/70 psi48 psi0.2294.4 gal

    Makers’ tables differ slightly. Follow the pump and tank instructions, and have a well contractor check a pump that short cycles. Results are estimates.

    Frequently asked questions

    What should my pressure tank precharge be?

    2 psi below the cut-in pressure of the pressure switch, measured with the tank drained and the pump off.

    What happens if the precharge is too low?

    The tank holds less usable water, so the pump starts more often. Very low or zero precharge usually means a failed bladder.

    How often should I check the precharge?

    Once a year is a good habit, and any time the pump starts cycling quickly.

    Is PressureTankCalc free?

    Yes, with no sign-up or ads.

    Are my numbers saved?

    Yes, in this browser only.